Overview
ASD 532
It has the same technical specifications as the ASD 535, but with just one sampling pipe and a more compact fan. Anyone familiar with the ASD 535 will find added monitoring using the ASD 532 a breeze.
Configuration and maintenance of the detector are made in the same simple way.

Technical information
Aesthetically, the ASD 532 is very subtle and discreet – just like all devices in the ASD range. Once installed in hollow spaces, the sampling pipes are completely invisible, while the flush-mounted sampling holes are often imperceptible.
The installation is carried out with the highest possible level of adaptation to the surroundings in question. The sampling pipe can be laid out asymmetrically, which means it blends seamlessly into the structure of the building. This eliminates the need for long sampling pipes and thus reduces costs.
Key Features
- ASD 532 - Aspirating smoke detector for 1 SSD 532 smoke sensor without smoke level indicator
- ASD 532-3 - Smoke sensor 0.02-10%/m alarm sensitivity (0.00087 dB/m)
For medium-sized premises:
- Compact Design
- Permissable Temperature Range: - 20.c to +60.c
- Maximum sampling pipe length: 120 m
- Ethernet or RS-485 networking
- Approvals: VdS, UL*, FM*
Applications
The ASD 532 is ideal for property and space surveillance thanks to its excellent response behaviour. Typical applications include:
Room surveillance
- Museums, galleries, theatres, cinemas
- Cultural artefact collections, historical buildings
- Informatics and computer centres
- Telecommunication centres
- Laboratory and Research Centres
- Electronic Measuring Rooms
- Transformer Rooms
- Clean Rooms
- Refridgerated Warehouses
Property surveillance
- Telecommunication facilities
- High and low-voltage distribution cabinets
- Display cases
- IT installations
- CNC control systems
Invisible surveillance
- Protection of cultral assets
- Prison cells
Modules & Accessories
Optional Modules:
- RIM 36 - Optional module with 5 Additional Relays
- SD Card - Industrial SD card
- SIM 35/SMM 535 - RS 485 networking module/RS 485 master module
- UMS 35 - Universal module support for mounting line modules
- ASD PipeFlow - PC tool for drawing and calculating the sampling pipe
Accessories:
An extensive range of accessories are available (25 mm and ¾" sampling tube, sampling points, filters, water separators, etc.).
View the range of Securiton Pipes & Fittings that Patol offer alongside the ASD 532.
Technical Data
Supply Voltage Range | EN 54 FM/UL |
14.0-30 VDC 16.4-27 VDC |
Power Consumption | Typical For 24 VDC | 115 mA |
Sampling Tubes/Smoke Sensors | Quantity | 1 |
Alarm Sensitivity | Alarm Pre-Signal |
0.02-10%/m From 0.002%/m |
Alarm Levels | 5 (3 Pre-Signals, Alarm, Alarm 2) Adjustable Pre-Signal 10-90% |
|
Autolearning, Day/Night Switching | Configurable | |
Relays |
1-Channel Vers. 2-Channel Vers. Contact Load |
2 (1 Alarm, 1 Fault) (Use RIM 36 for Pre-Signals) 50 VDC/1 A (UL 30VDC) |
Interfaces |
O.C. Outputs PC Tool Network Inputs |
See Relays Ethernet RS 485, Ethernet Reset, Day/Night |
Optional Modules |
Quantity Types |
2 2/1 RIM 36, SIM 35 |
Standards/Approvals |
EN 54-20 EN 54-27 (Ventil, Ducts) UL 268, FM 3230 Other Compliance |
VdS G 215 101 Yes Planned - EMC, CPR, RoHS |
Number of Campling Apetures (with ASD PipeFlow) |
EN 54-20 Class A EN 54-20 Class B EN 54-20 Class C NFPA 72 (UL/FM) |
8 12 16 16 |
Monitoring Area | Max.Area | 1280 m2 |
System Limits as per EN 54-20 Class C |
Max. Quantity Sampling Apertures Max. Length to Last Sampling Point Max. Overall Length for all Sampling Tubes |
16 70m 120m |
System Limits without Conformity to Standards | Max. Overall Length for All Sampling Tubes | - |
Configuration |
Close Operation PC Tool |
EasyConfig ASD Config |
Fan/Sampling System |
Suction Pressure Service Life (MTTF) Performance Levels Suction Noise Soundproof Housing |
> 180 Pa > 80, 000 h (at 40.C) 3 <32 db="" a="" fan="" level="" 1=""> < 20 dB (A)
|
Housing |
EN 60529 Prot. Category Dimensions ( W x H x D) Weight (Approx.) Cable Entries |
IP 54 195 X 290 X 140 mm 1950g 3 x M20, 1 X M25 |
Operating Temperature/Humidity | Evaluation Unit | -20 - +60.C/95% RH (Amb. Air Max. +40.C) |
Display and Operation - Standard | Per Channel | 1 < |
Display and Operation - Enhanced | 10 LEDs (Yellow) for Smoke Level Indicator | Yes |
Event Menory/ Analogue Values |
On Board With SD Card |
1000 Events Up To 1 Year On-Board slot for SD Card |
For more information
Please visit our Technical Library