ASD 532

The ASD 532 is used for reliable monitoring of small and medium-sized areas and premises.

Overview

ASD 532

It has the same technical specifications as the ASD 535, but with just one sampling pipe and a more compact fan. Anyone familiar with the ASD 535 will find added monitoring using the ASD 532 a breeze.

Configuration and maintenance of the detector are made in the same simple way.

View our Technical Library

asd 532 aspirating smoke detector

Technical information

Aesthetically, the ASD 532 is very subtle and discreet – just like all devices in the ASD range. Once installed in hollow spaces, the sampling pipes are completely invisible, while the flush-mounted sampling holes are often imperceptible.

The installation is carried out with the highest possible level of adaptation to the surroundings in question. The sampling pipe can be laid out asymmetrically, which means it blends seamlessly into the structure of the building. This eliminates the need for long sampling pipes and thus reduces costs.

Key Features

  • ASD 532 - Aspirating smoke detector for 1 SSD 532 smoke sensor without smoke level indicator
  • ASD 532-3 - Smoke sensor 0.02-10%/m alarm sensitivity (0.00087 dB/m)

For medium-sized premises:

  • Compact Design
  • Permissable Temperature Range: - 20.c to +60.c
  • Maximum sampling pipe length: 120 m
  • Ethernet or RS-485 networking
  • Approvals: VdS, UL*, FM*

Applications

The ASD 532 is ideal for property and space surveillance thanks to its excellent response behaviour. Typical applications include:

Room surveillance

  • Museums, galleries, theatres, cinemas
  • Cultural artefact collections, historical buildings
  • Informatics and computer centres
  • Telecommunication centres
  • Laboratory and Research Centres
  • Electronic Measuring Rooms
  • Transformer Rooms
  • Clean Rooms
  • Refridgerated Warehouses

Property surveillance

  • Telecommunication facilities
  • High and low-voltage distribution cabinets
  • Display cases
  • IT installations
  • CNC control systems

Invisible surveillance

  • Protection of cultral assets
  • Prison cells

Modules & Accessories

Optional Modules:

  • RIM 36 - Optional module with 5 Additional Relays
  • SD Card - Industrial SD card
  • SIM 35/SMM 535 - RS 485 networking module/RS 485 master module
  • UMS 35 - Universal module support for mounting line modules
  • ASD PipeFlow - PC tool for drawing and calculating the sampling pipe

Accessories:

An extensive range of accessories are available (25 mm and ¾" sampling tube, sampling points, filters, water separators, etc.).

View the range of Securiton Pipes & Fittings that Patol offer alongside the ASD 532.

Technical Data

Supply Voltage Range EN 54
FM/UL
14.0-30 VDC
16.4-27 VDC
Power Consumption Typical For 24 VDC 115 mA
Sampling Tubes/Smoke Sensors Quantity 1
Alarm Sensitivity Alarm
Pre-Signal
0.02-10%/m
From 0.002%/m
Alarm Levels   5 (3 Pre-Signals, Alarm, Alarm 2)
Adjustable Pre-Signal 10-90%
Autolearning, Day/Night Switching   Configurable
Relays

1-Channel Vers.

2-Channel Vers.

Contact Load

2 (1 Alarm, 1 Fault)

(Use RIM 36 for Pre-Signals)

50 VDC/1 A (UL 30VDC)

Interfaces

O.C. Outputs

PC Tool

Network

Inputs

See Relays

Ethernet

RS 485, Ethernet

Reset, Day/Night

Optional Modules

Quantity

Types

2

2/1 RIM 36, SIM 35

Standards/Approvals

EN 54-20

EN 54-27 (Ventil, Ducts)

UL 268, FM 3230

Other

Compliance

VdS G 215 101

Yes

Planned

-

EMC, CPR, RoHS

Number of Campling Apetures (with ASD PipeFlow)

EN 54-20 Class A

EN 54-20 Class B

EN 54-20 Class C

NFPA 72 (UL/FM)

8

12

16

16

Monitoring Area Max.Area 1280 m2
System Limits as per EN 54-20 Class C

Max. Quantity Sampling Apertures

Max. Length to Last Sampling Point

Max. Overall Length for all Sampling Tubes

16

70m

120m

System Limits without Conformity to Standards Max. Overall Length for All Sampling Tubes -
Configuration

Close Operation

PC Tool

EasyConfig

ASD Config

Fan/Sampling System

Suction Pressure

Service Life (MTTF)

Performance Levels

Suction Noise

Soundproof Housing

> 180 Pa

> 80, 000 h (at 40.C)

3

<32 db="" a="" fan="" level="" 1="">

< 20 dB (A)

 

Housing

EN 60529 Prot. Category

Dimensions ( W x H x D)

Weight (Approx.)

Cable Entries

IP 54

195 X 290 X 140 mm

1950g

3 x M20, 1 X M25

Operating Temperature/Humidity Evaluation Unit -20 - +60.C/95% RH (Amb. Air Max. +40.C)
Display and Operation - Standard Per Channel 1 <> LED Green, 1 Red <> LED, 1 Yellow <> LED, 1 Yellow Soiling LED, 1 Reset Key
Display and Operation - Enhanced 10 LEDs (Yellow) for Smoke Level Indicator Yes
Event Menory/ Analogue Values

On Board

With SD Card

1000 Events

Up To 1 Year On-Board slot for SD Card

For more information

Please visit our Technical Library

View Technical Library