The 5010
Sensor unit is equipped with a spigot for connection to a
flexible hose. If an 'on site' air supply capable of delivering
5.0 ltrs/sec at this connection is not available a Series 5000 Air
Purge Unit should be employed. These units are equipped with an
easily removable and washable air filter, however these filters
are intended to preserve blower life in normal conditions.
The blower should either be installed outside the dirty/dusty area
or the unit inlet piped to a clean air environment. Intermediate
rigid ducting is most readily achieved by the use of standard
µPVC pipes and fittings. 2 m of hose is provided with each
purge unit for couplings at sensor & blower.
Note
: Type 5011 Sensors have a 1/4"NPT air fitting and require
a 2 Bar (30 PSI) air supply. Type 5040, 5041 & 5042 Blowers are not suitable for 5011 Sensor Heads.
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
TYPICAL BLOWER
- TYPE 5041
|
|
|
|
|
|
|
|
|
|
|
|
5000 Series
Air Purge Units are multi stage centrifugal fan blowers which can
be supplied in a variety of configurations. These include both 1
& 3 phase supplies at 110, 230 & 380/440 Vac, a variety
of hose/duct connection arrangements, and high capacity units.
The type 5041 unit shown is:-
Supply:- 220/240 Vac 50 Hz
Power:- 50 VA (nominal)
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
GENERAL SPECIFICATION
Sensor/Controller
Supply Voltage:- 20 - 30 Vdc
Supply Current:-
35 mA Stand by
70 mA Max / Full Alarm
Indications:-
Detectors - 4 off - Red LEDs
Alarm - Red LED
Trip (S/D) - Red LED
Fault - 3 off - Yellow LEDs
(Air / Sensor / Auxiliary)
Supply On - Green LED
Outputs:-
Alarm Contact - 1 pole C/O
Trip Contact - 1 pole C/O
Fault Contact - 1 pole C/O
Rating - 30 Vdc / 120 Vac - 500 mA
Controls:-
Reset, Head Test & Lamp Test PBs
Program DIL switch.
Auxiliary input:- PSU / Charger etc.
DIL Switch :- System Operation Setting.
Sensitivity - 4 level
Voting / Latching / Auto Reset modes
PATOL LIMITED
Rectory Road, Padworth, Berkshire, UK.
Tel: 0118 9701701 Fax: 0118 9701700
Email:- patol.limited@ntlworld.com
|
|
|
|
|
|
|
Detectors :- 8 off
Configuration :- Interlaced as 4 channels
Sensitivity :- 10 to 40 uW adustable in four steps.
Spectral Filter :- 5 to 14 um
Transit Speed :- 1 to 6 m/s
Typical response to various size anomalies for a represenative conveyor installation :- |
|
|
| |